KT40-240/2P low voltage surge arrester designed for the transformer low-voltage side protection at distribution transformer secondary bushings, against the risk of the harmful effects of transient surges, to ensure the smooth operation of transformer.
| Model No. | KT40-240/2P |
| Güç Sistemi Birleşme | 120/240Vac(Split phase) |
| Maksimum sürekli çalışma voltajı (AC) MOCV | 420 Vac(460 Vac as option ) |
| Nominal deşarj akımı (8/20us) Gir | 5KA |
| Maksimum deşarj akımı (8/20us) Imax | 40KA |
KT40-240/2P LV surge arrester adopts UL certified high-perfomance MOV as the core components, with high surge discharge capacity and low voltage protectionlevel. lt can effectively suppress the transient over voltage on power line caused by lightning strikes and other electrical source.
KT40-240/2P is designed for the transformer low-voltage side protection at distribution transformer secondary bushings, against the risk of the harmful effects of transient surges, to ensure the smooth operation of transformer.
The KT40-240/2P use high grade 304# stainless steel (with Chromium plating) as frame holder, and use PC/ABS Alloy materials as enclosure housing with a tight waterproof and flame resistant package. lt is ideal for long term use in harsh natural exposure environments.
| Model No. | KT40-240/2P | |
|---|---|---|
| Tip | Hafif Görev (dış mekan tipi) Mükemmel hava koşullarına dayanıklı | |
| Uygun olarak | IEEE Std C62.11,UL1449 4. baskı | |
| Güç Sistemi A | 120/240Vac(Split phase | |
| Frekans | 50/60Hz | |
| Maksimum sürekli çalışma voltajı (AC)MOCV | 420 Vac(460 Vac as option) | |
| Nominal deşarj akımı (8/20us) içinde | 5kA | |
| Maksimum deşarj akımı (8/20us) lmax | 40kA | |
| Voltaj impulsu (1.2/50us) BlL Dilek | 10kV | |
| Maksimum Deşarj Voltajı (KV Krest) 8/20 μs Akım Dalgası | @3kA | <1.6kV Max |
| @5kA | < 1.7ky Max | |
| @20kA | < 2.2kV Max | |
| @40kA | < 2.6kV Max | |
| Sızıntı akımı IL | <0.1mA | |
| Güç Frekansı Testi 50/60HZ | Kuru : ≥10 KV rms (1 dakika) Islak : ≥6KV rms (10 saniye) | |
| Çalışma sıcaklığı aralığı | -40°C~ 85°C | |
| Kablo Bağlantısı | L: Siyah tel; N/G: beyaz tel Her tel 1 adet Lug(5.5-12) veya (5.5-16) ile | |
| Kablo spesifikasyonu | UL1015 10AWG: 390mm (terminal deliğine kadar uzunluk) | |
| destek çerçevesi | 304# paslanmaz çelik (krom kaplama ile) | |
| Boyut (HxWxD) | 131.4x45.5x27.5mm | |
| Koruma konutu malzemesi | (Polikarbonat) PC/ABS Alaşımı - 40°C~ 100°C (Alev geciktirici derecesi: UL94/V-0) | |
| Yalıtım Malzemesi | Epoksiresen 25KV/mm -40°C~ 160°C | |
| Koruma derecesi | IP68 (veya NEMA6P) | |


S1: Tek fazlı düşük voltajlı bir patlama durdurucusunun nominal deşarj akımı nasıl belirlenir?
A1:It is determined based on the possible overvoltage conditions and protection requirements of the system. Generally, for a 480V system, products with a nominal discharge current (In) of 5kA – 20kA can be selected. If the system is located in an area with frequent lightning activities, a larger value should be chosen.
S2: Tek fazlı düşük voltajlı bir patlama durdurucusunun tepki süresi nedir?
C2: Modern çinko oksit aşırı gerilim durdurucuları genellikle nanosaniye aralığında tepki süresine sahiptir; bu da aşırı voltaja çok kısa sürede yanıt verebilir ve akımı hızlıca iletebiliyor. Genellikle, birkaç nanosaniye ile onlarca nanosaniye arasında olabilir.
S3: Eğer aşırı patlayıcı hizmet ömrüne ulaşmadıysa ancak birden fazla yıldırım çarpması yaşadıysa, değiştirilmesi gerekiyor mu?
C3: Belirli koşullara göre değerlendirilmesi gerekir. Eğer aşırı devre kesici bir aşırı sayacıyla donatılmışsa, sayının üreticinin belirttiği nominal sınırı aşıp aşmadığını kontrol edebilirsiniz. Eğer sayı sınıra yakın veya onu aşıyorsa veya test sırasında performans bozulması (örneğin aşırı sızdırma akımı gibi) tespit edilirse, devre durdurucu hizmet süresine ulaşmamış olsa bile değiştirilmek üzere değerlendirilmelidir.